:Supply
Mains voltage (L1, L2, L3)
MCD5-xxxx-T5 200 VAC ~ 525 VAC (± 10%)
MCD5-xxxx-T7 380 VAC ~ 690 VAC (± 10%)
(earthed star supply system only)
MCD5-xxxx-T7 380 VAC ~ 600 VAC (± 10%) (inside delta connection)
Control voltage (terminals A4, A5, A6)
CV1 (A5, A6) 24 VAC/VDC (± 20%)
CV2 (A5, A6) 110~120 VAC (+ 10% / - 15%)
CV2 (A4, A6) 220~240 VAC (+ 10% / - 15%)
Mains frequency 50/60 Hz (± 10%)
Rated insulation voltage to earth 600 VAC
Rated impulse withstand voltage 4 kV
Form designation Bypassed or continuous, semiconductor motor
starter form 1
Short circuit capability
Coordination with semiconductor fuses Type 2
Coordination with HRC fuses Type 1
MCD5-0021B to MCD5-0105B prospective current 10 kA
MCD5-0131B to MCD5-0245C prospective current 18 kA
MCD5-0360C to MCD5-0927C prospective current 85 kA
MCD5-1200C to MCD5-1600C prospective current 100 kA
Electromagnetic capability (compliant with EU Directive 89/336/EEC)
EMC Emissions (Terminals 13 & 14) IEC 60947-4-2 Class B and
Lloyds Marine No. 1 Specification
EMC Immunity IEC 60947-4-2
Outputs
Relay Outputs 10A @ 250 VAC resistive, 5A
@ 250 VAC AC15 pf 0.3
Programmable Outputs
Relay A (13, 14) Normally open
Relay B (21, 22, 24) Changeover
Relay C (33, 34) Normally open
Analogue Output (07, 08) 0 – 20 mA or 4 – 20 mA ( selectable)
Maximum load 600 Ω (12 VDC @ 20 mA) (accuracy ± 5%)
24 VDC Output (16, 08) Maximum load 200 mA (accuracy ± 10%)
:Environmental
Protection MCD5-0021B ~ MCD5-0105B IP 20 & NEMA, UL Indoor Type 1
Protection MCD5-0131B ~ MCD5-1600C IP 00, UL Indoor Open Type
Operating temperature -10° C to 60° C, above 40° C with derating
Storage temperature - 25° C to + 60° C
Operating Altitude 0 – 1000 m, above 1000 m with derating
Humidity 5% to 95% Relative Humidity
Pollution degree Pollution Degree 3
Heat Dissipation
During start 4.5 watts per ampere