سافت استارتر مدیوم ولتاژ MEDIUM VOLTAGE SOFT STARTER CENTRIS
سافت استارتر مدیوم ولتاژ MEDIUM VOLTAGE SOFT STARTER CENTRIS Range 2.3 kV – 15kV Centris is the fully featured medium voltage soft start motor controller
مشخصات
- شرکت سازنده :
- FAIRFORD ELECTRONICS
- مدل :
- CENTRIS
- کشور سازنده :
- ایالات متحده آمریكا
- 2300V – 7200V 60kV :
- 11000V-15000V 110KV
توضیحات محصول
Technical Data
Type of Load
3-phase medium voltage AC induction or synchronous motors
AC Supply Voltage
2300, 3300, 4160, 6000/7200V, 11-15kV
VAC +10% to -15%, 50/60 Hz line voltages
HP Ratings
Up to 10,000 HP @ 7.2kV (1500 Amps)
Up to 20,000 HP @ 15kV (800 Amps)
Contact Fairford Electronics for higher rating requirements
Overload Rating
AC53b 600-30-60m
Power Circuits
Series strings of SCR power modules (1, 2 or 3 matched pairs of SCRs per phase depending on voltage rating)
SCR Peak Inverse Voltage
Line Voltage PIV Rating Line Voltage PIV Rating
2300 6500 6500 19500
3300 9000 6900-7200 26000
4160 13000 11000 27000
6000 18000 13-15kV 39500
BIL Rating
2300V – 7200V 60kV
11000 – 15000V (110kV)
Transient Voltage Protection
dv/dt circuits (1 per SCR pair)
Vacuum Bypass Contactor
Standard on all models, line start rated
Ambient Operating Conditions
0 – 50°C (82° F to 122° F) (Optional -20° to 50° C with heaters)
5 – 95% relative humidity
0 – 3300 ft (1000m above sea level without derating)
Digital Control Unit (DCU)
Programmable keypad/operator with 2 lines x 20
character backlit LCD display. Status/Alarm
LEDs (indicate: Power, Run, Alarm, Trip, Aux 1 – 8)
Auxiliary Contacts
Multiple Form C contacts rated 5A @ 250VAC max.
6 fully programmable relays (including fail-safe operation)
5 dedicated relays (fault, at-speed, etc.)
Programmable Features
Motor FLA, service factor, insulation class
Dual Ramp Adjustments – Two independent settings for:
– Initial Torque 0 – 100% of nominal torque, voltage or current
– Current Limit 200 – 600% of motor FLA
– Acceleration Time 1 – 120 seconds
Power Ramp Function
Three Custom Curves Via plotted torque/time axis points
Pump-Flex™ Deceleration 1 – 60 seconds with begin & end torque adj
Kick Start 0.1 – 2.0 seconds (10 – 100% voltage)
Tach Feedback (option) Closed loop speed ramp
Motor and Starter Protection
Electronic Overload Phase Loss
Phase Imbalance Phase Reversal
Short Circuit Detection Over / Under Current
Over / Under Voltage Shorted SCR / Shunt Trip
Starter Over-Temp Coast Down Lockout
Starts per Hour Lockout Time between starts
RTD Input (Option) Ground Fault (Option)
Statistical Data
Elapsed run time, last start time, average starting current, stores history of up to 60 events (data includes date & time, phase & ground fault current). Also displays time-to-trip, remaining inhibit time and starts/hour values
Metering (Voltage & Current)
Percent of FLA, phase currents, kVAR, kVA, kW, power factor, demand, avg. start current, remaining thermal register, thermal capacity to start, measured capacity to start, time since last start, line frequency, phase order, RTD values (optional).
Enclosure
NEMA 12 with 3R optional (not for direct sun applications), top and bottom entrance plates, 11 gauge steel, ASA #61 gray powder coated paint.
Communications
RS485 with Modbus RTU protocol or RS232 with windows interface.