رله ایمنی هوشمند SMART RELAY GM INTERNATIONAL GMI D5295S
رله ایمنی SIL3 تک کاناله SIL 3 Certified Safety Relay for Hazardous Area D5295S, قابلیت Line Monitoring
مشخصات
- D1092D :
- SIL3 Relay D1000 2 Ch, 4SPST, 3A
- D5095S :
- SIL3 Relay D5000 1 Ch, NE/ND 2 SPST, 5A
- D5094S :
- SIL3 Relay D5000 1 Ch, NE/ND 2 SPST, 5A
- D1092S :
- SIL3 Relay D1000 1 Ch, 2SPST, 3A
- D5091S :
- SIL3 Relay D5000 1 Ch, ND SPST, 5A
- D5090S :
- SIL3 Relay D5000 1 Ch, NE SPST, 5A
- D5294S :
- SIL3 Relay D5000 1 Ch, ND 1+1SPST, 5A
- D1093S :
- SIL3 Relay D1000 1 Ch, 2SPST, 3A Line de
قیمت محصول
- حداقل مقدار سفارش :
- 1 عدد
توضیحات محصول
رله ایمنی مدل D5295S
4A SIL 3 NC contact Relay Out Module for NE or
F&G/ND Load with full diagnostic and Modbus,
DIN-Rail and Term. Board Model D5295S
General Description: The D5295S is a relay module suitable for the switching of safety
related circuits, up to SIL 3 level according to IEC 61508:2010 Ed. 2 for high risk industries.
It provides isolation between input and output contacts.
A wide compatibility towards different DCS/PLC is guaranteed: driving line pulse testing,
executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and
LED flickering.
Internal relay coil short circuit is detected from module.
D5295S has 2+2 SPST relay contacts connected in parallel and then in series to avoid
spurious trip and to increase availability (see function diagram).
High availability SIL 3 Safety Function for NE load or F&G / ND load is available at Terminal
Blocks 13-14.
When the driving signal is high (24 Vdc), the relay is energized, contacts at terminals
13-15 and 14-16 are open and load is de-energized.
When the driving signal is low (0 Vdc), the relay is de-energized, contacts at terminals
13-15 and 14-16 are closed, the load is energized
در صورت نیاز به اطلاعات بیشتر با نمایندگی جی ام آی تماس بگیرید.