| Electrical data |
| Operating voltage [V] |
26.5...31.6 DC |
| Max. current consumption from AS-i [mA] |
250 |
| Max. current load total [A] |
2 |
| Integrated watchdog |
yes |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital inputs: 4; Number of digital outputs: 4 |
| Inputs |
| Number of digital inputs |
4 |
| Input circuit of digital inputs |
PNP |
| Sensor supply of the inputs |
AS-i |
| Voltage supply [V] |
18...30; (via flat cable) |
| Max. total current rating of inputs [mA] |
200 |
| Input current High [mA] |
6...10 |
| Input current low [mA] |
0...2 |
| Min. switching level high signal [V] |
11 |
| Digital inputs protected against short circuits |
yes |
| Outputs |
| Electrical design |
AS-i |
| Number of digital outputs |
4 |
| Circuit |
PNP |
| Voltage range DC [V] |
15...30; (to PELV; via flat cable; for cULus the voltage must comply with the values specified in "Limited Voltage/Current") |
| Max. current load per output [mA] |
1000; (utilization category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1); according to cULus: 700 mA) |
| Short-circuit proof |
yes |
| Electrically separated |
yes |
| Operating conditions |
| Ambient temperature [°C] |
-25...70 |
| Protection |
IP 67 |
| Tests / approvals |
| EMC |
|
| MTTF [years] |
171 |
| AS-i classification |
| AS-i version |
2.1 |
| AS-i addressing |
IR addressing possible |
| Extended addressing mode |
no |
| AS-i profile |
S-7.0.E |
| AS-i I/O configuration [hex] |
7 |
| AS-i ID code [hex] |
0.E |
| AS-i certificate |
39301 |
| Data bits |
| Data bit |
D0 |
D1 |
D2 |
D3 |
| Input |
1 |
2 |
3 |
4 |
| Socket |
I-1 |
I-2 |
I-3 |
I-4 |
| Pin |
2+4 |
2+4 |
2+4 |
2+4 |
| Output |
1 |
2 |
3 |
4 |
| Socket |
O-1 |
O-2 |
O-3 |
O-4 |
| Pin |
4 |
4 |
4 |
4 |
|
| Mechanical data |
| Weight [g] |
192 |
| Type of mounting |
AS-i interface to FC-E lower parts |
| Material |
PBT |
| Displays / operating elements |
| Display |
| Power |
LED, green |
| errors |
LED, red |
| Function |
LED, yellow |
|
| Accessories |
| Accessories (optional) |
|
| Remarks |
| Remarks |
| Inputs and outputs must be electrically isolated. |
| Do not connect any of the following points to an external potential: |
| I-, I+, I1, I2, I3, I4 |
| The connections are electrically connected with the AS-i cable. |
|
| Pack quantity |
1 pcs. |
| Electrical connection |
|
contact pins to module lower part, FK-E: |
|
Connector: M12 |